PART NO : 6020-003-03 DESC : AUTO MAINS (Utility) FAILURE CONTROL MODULES BRAND : DSE USE : STANDART ENGINE AND ELECTRONIC CAN-BUS VARIANTS INFO : Specification DC SUPPLY CONTINUOUS VOLTAGE RATING : 8 V to 35 V Continuous CRANKING DROPOUTS : Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT : 100 mA at 12 V, 105 mA at 24 V MAXIMUM STANDBY CURRENT : 60 mA at 12 V, 55 mA at 24 V MAXIMUM SLEEP CURRENT : 40 mA at 12 V, 35 mA at 24 V GENERATOR & MAINS (UTILITY) VOLTAGE RANGE : 15 V to 415 V AC (Ph to N), 26 V to 719 V AC (Ph to Ph) FREQUENCY RANGE : 3.5 Hz to 75 Hz INPUTS DIGITAL INPUTS A to F : Negative switching ANALOGUE INPUTS A to C : Configurable as: Negative switching digital input : 0 Ω to 480 Ω ANALOGUE INPUT D Configurable as : Negative switching digital input 0 V to 10 V, 4 mA to 20 mA, 0 Ω to 480 Ω OUTPUTS OUTPUT A (FUEL) : 10 A short term, 5 A continuous, at supply voltage OUTPUT B (START) : 10 A short term, 5 A continuous,at supply voltage AUXILIARY OUTPUTS C, D, E & F : 2 A DC at supply voltage